Features
Reliability & High performance
- Acquired KERI test report for KOEMA 0930/0931/0932 standard criteria
- Arc removal time: within 5ms (when Arc Eliminator is applied)
- Guarantees minimum # of operation of Arc Eliminator (electrically 2 times / mechanically 10 times)
Expandability
- Arc protection for multiple power supply system through optical communication link between APRs
- APS 1 set can protect up to 25 switchgears
- Applicable to new installations and existing switchgears (Retrofit)
Flexibility & User-friendly design
- Possible to select a solution that suits the customer situation
- APR/AEC/AE in one panel
※ APR : Arc Protection Relay, AEC : Arc Eliminator Controller, AE : Arc Eliminator
Reliability & High performance
- Acquired KERI test report for KOEMA 0930/0931/0932 standard criteria
- Arc removal time: within 5ms (when Arc Eliminator is applied)
- Guarantees minimum # of operation of Arc Eliminator (electrically 2 times / mechanically 10 times)
Expandability
- Arc protection for multiple power supply system through optical communication link between APRs
- APS 1 set can protect up to 25 switchgears
- Applicable to new installations and existing switchgears (Retrofit)
Flexibility & User-friendly design
- Possible to select a solution that suits the customer situation
- APR/AEC/AE in one panel
※ APR : Arc Protection Relay, AEC : Arc Eliminator Controller, AE : Arc Eliminator
Specification
Rating | Unit | Specification | |
---|---|---|---|
Rated voltage | kV | 7.2 / 12 | 24 |
Rated current | A | Regardless of current (Current does not flow during normal operation) |
|
Power frequency withstand voltage | kV rms/1min | 28 | 50 |
Lightning impulse withstand voltage | kV peak | 75 | 125 |
Rated short time current | kA/s | 40 | |
Fault current bypass time | < 5ms after confirming the accident | ||
Installing Arc Eliminator | Cradle method | ||
Interlock | When AE is in closing state, prevent cradle from racking in (Improve worker safety) |
||
Applied standard | KOEMA 0932 |
Rating | Unit | Specification | |
---|---|---|---|
Rated voltage | kV | 7.2 / 12 | 24 |
Rated current | A | Regardless of current (Current does not flow during normal operation) |
|
Power frequency withstand voltage | kV rms/1min | 28 | 50 |
Lightning impulse withstand voltage | kV peak | 75 | 125 |
Rated short time current | kA/s | 40 | |
Fault current bypass time | < 5ms after confirming the accident | ||
Installing Arc Eliminator | Cradle method | ||
Interlock | When AE is in closing state, prevent cradle from racking in (Improve worker safety) |
||
Applied standard | KOEMA 0932 |
System Configuration

Components | Main features | |
---|---|---|
Arc protection relay |
· Quickly determining accidents using optical signal and current signal · Arc Eliminator input and output command within 1.5ms · CB Trip command output time reduction through applying high-speed semiconductor devices (HSO, High speed output) - HSO: ≤ 1.5 ms - Conventional contact: ≤ 15 ms |
|
Slave unit | Point | · Arc accident detection and location identification through point sensor |
Loop | · Detecting broad area arc accident through loop sensor | |
Selective |
· Arc accident detection and location identification through point sensor · Apply high-speed semiconductor contact point (HSO, High speed output) · Arc protection can be performed solely without APR |
|
Arc eliminator controller |
· AE operation by receiving APR operation command through optical communication · Output of drive current within 0.6±0.1 ms |
|
Arc eliminator |
· In case of an arc accident, bypass the fault current and
extinguish the arc by grounding and short-circuiting the three-phase system · Input within 3.5ms after receiving operation command (Including AEC operation time) |

Components | Main features | |
---|---|---|
Arc protection relay |
· Quickly determining accidents using optical signal and current signal · Arc Eliminator input and output command within 1.5ms · CB Trip command output time reduction through applying high-speed semiconductor devices (HSO, High speed output) - HSO: ≤ 1.5 ms - Conventional contact: ≤ 15 ms |
|
Slave unit | Point | · Arc accident detection and location identification through point sensor |
Loop | · Detecting broad area arc accident through loop sensor | |
Selective |
· Arc accident detection and location identification through point sensor · Apply high-speed semiconductor contact point (HSO, High speed output) · Arc protection can be performed solely without APR |
|
Arc eliminator controller |
· AE operation by receiving APR operation command through optical communication · Output of drive current within 0.6±0.1 ms |
|
Arc eliminator |
· In case of an arc accident, bypass the fault current and
extinguish the arc by grounding and short-circuiting the three-phase system · Input within 3.5ms after receiving operation command (Including AEC operation time) |