Features
Stability and Reliability
- Complied with IEC 61439-1&2 standard
- Obtained ASTA certificate of verification tests
Safety and Convenience
- Internal arc-tested design(85kA/0.5s, according to IEC 61641)
- Form 4b structure(Prevention fault spread by metal and insulated partitions)
- Degrees of protection
- IP43(outside), IP2X(inside)
- Mechanical impact : IK07
- Heat flow structure
- Sufficient ventilation structure both inside and out
- Specially designed arc release cover for heat dissipation
Compact Size and Flexible Structure
- Main busbars are located in the middle section of the MDB
- Easy to place two ACBs on the panel
- Panel size reduced compared to that of others
- Modular structure, excellent assemblability
Adopted LS ELECTRIC ACB & MCCB
- LS ELECTRIC low voltage devices are complied with all applicable standards
- ACB : Fully lined-up up to 6300A and 150kA
- MCCB : Fully lined-up up to 1600A and 150kA@415Vac
Stability and Reliability
- Complied with IEC 61439-1&2 standard
- Obtained ASTA certificate of verification tests
Safety and Convenience
- Internal arc-tested design(85kA/0.5s, according to IEC 61641)
- Form 4b structure(Prevention fault spread by metal and insulated partitions)
- Degrees of protection
- IP43(outside), IP2X(inside)
- Mechanical impact : IK07
- Heat flow structure
- Sufficient ventilation structure both inside and out
- Specially designed arc release cover for heat dissipation
Compact Size and Flexible Structure
- Main busbars are located in the middle section of the MDB
- Easy to place two ACBs on the panel
- Panel size reduced compared to that of others
- Modular structure, excellent assemblability
Adopted LS ELECTRIC ACB & MCCB
- LS ELECTRIC low voltage devices are complied with all applicable standards
- ACB : Fully lined-up up to 6300A and 150kA
- MCCB : Fully lined-up up to 1600A and 150kA@415Vac
Specification
Rating | Unit | ACB Panel | MCCB Panel | |
---|---|---|---|---|
Rated operating voltage | V | 690 | 440 | |
Rated frequency | Hz | 50 / 60 | 50 / 60 | |
Busbar (Rated current) |
Main | A | 2000, 2500, 3200, 4000, 5000 | |
Vertical | A | 1800, 2000, 2500, 3200, 4000, 5000 | ||
Rated short time withstand current | kA/s | Up to 100kA/1s, 65kA/3s | ||
Rated insulated voltage | V | 1000 | 750 | |
Rated impulse withstand voltage | kV | 12 | 8 | |
Form of internal separation | Form 4b | |||
Degree of protection | Up to IP43 | |||
Standard | IEC 61439-1 & 2 |
Rating | Unit | ACB Panel | MCCB Panel | |
---|---|---|---|---|
Rated operating voltage | V | 690 | 440 | |
Rated frequency | Hz | 50 / 60 | 50 / 60 | |
Busbar (Rated current) |
Main | A | 2000, 2500, 3200, 4000, 5000 | |
Vertical | A | 1800, 2000, 2500, 3200, 4000, 5000 | ||
Rated short time withstand current | kA/s | Up to 100kA/1s, 65kA/3s | ||
Rated insulated voltage | V | 1000 | 750 | |
Rated impulse withstand voltage | kV | 12 | 8 | |
Form of internal separation | Form 4b | |||
Degree of protection | Up to IP43 | |||
Standard | IEC 61439-1 & 2 |