C-AIS
Home
Smart Power Solution
Power Distribution
MV SWGR
Features
Reliability
- Type testing is completed according to IEC62271-200
- Internal arc proofed 21kA/1sec A-FLR
- Earthing of both the entire switchboard structure and the metal division between compartments
- Mechanical interlocks assure exact operation sequence
- Protection classes: PI (insulating partition)
- Loss of service continuity classes: LSC2A (LSC1 for bus riser)
- IP3X protection degree on the external housing
Optimization
- Reduced dimension and weight
- Less space requirement for switchboard installation
- Easy integration in factory-built outdoor substations
- Adapted solutions to cable connection
- Modular units containing fixed and withdrawable metal-enclosed switchgear, using vacuum
Simplicity
- Simplified switchboard busbar design
- Mimic diagram in front of the switchboard using simple and functional devices
Reliability
- Type testing is completed according to IEC62271-200
- Internal arc proofed 21kA/1sec A-FLR
- Earthing of both the entire switchboard structure and the metal division between compartments
- Mechanical interlocks assure exact operation sequence
- Protection classes: PI (insulating partition)
- Loss of service continuity classes: LSC2A (LSC1 for bus riser)
- IP3X protection degree on the external housing
Optimization
- Reduced dimension and weight
- Less space requirement for switchboard installation
- Easy integration in factory-built outdoor substations
- Adapted solutions to cable connection
- Modular units containing fixed and withdrawable metal-enclosed switchgear, using vacuum
Simplicity
- Simplified switchboard busbar design
- Mimic diagram in front of the switchboard using simple and functional devices
Specification
Rating |
Specification |
Rated voltage |
kV |
12 |
17.5 |
24 |
Rated frequency |
Hz |
50/60 |
Power frequency withstand voltage (Insulation/Isolation) |
kV, rms (1min) |
28 / 32 |
38 / 45 |
50 / 60 |
Lightning impulse withstand voltage (Insulation/Isolation) |
kV, peak ( 1.2 X 50 ㎲) |
75 / 85 |
95 / 110 |
125 / 145 |
Rated frequency |
A |
630 |
Short-time withstand current |
kA/s |
16kA/3s, 21kA/3s, 25kA/1s |
Making capacity (50Hz) |
kA |
40 / 50 / 54.6 |
Internal arc classification |
kA/1s |
21 (A-FLR): Option |
Rating |
Specification |
Rated voltage |
kV |
12 |
17.5 |
24 |
Rated frequency |
Hz |
50/60 |
Power frequency withstand voltage (Insulation/Isolation) |
kV, rms (1min) |
28 / 32 |
38 / 45 |
50 / 60 |
Lightning impulse withstand voltage (Insulation/Isolation) |
kV, peak ( 1.2 X 50 ㎲) |
75 / 85 |
95 / 110 |
125 / 145 |
Rated frequency |
A |
630 |
Short-time withstand current |
kA/s |
16kA/3s, 21kA/3s, 25kA/1s |
Making capacity (50Hz) |
kA |
40 / 50 / 54.6 |
Internal arc classification |
kA/1s |
21 (A-FLR): Option |