Features

Reliability
  • Type testing is completed according to IEC62271-200
  • Internal arc proofed 21kA/1sec A-FLR
  • Earthing of both the entire switchboard structure and the metal division between compartments
  • Mechanical interlocks assure exact operation sequence
  • Protection classes: PI (insulating partition)
  • Loss of service continuity classes: LSC2A (LSC1 for bus riser)
  • IP3X protection degree on the external housing
Optimization
  • Reduced dimension and weight
  • Less space requirement for switchboard installation
  • Easy integration in factory-built outdoor substations
  • Adapted solutions to cable connection
  • Modular units containing fixed and withdrawable metal-enclosed switchgear, using vacuum
Simplicity
  • Simplified switchboard busbar design
  • Mimic diagram in front of the switchboard using simple and functional devices
Reliability
  • Type testing is completed according to IEC62271-200
  • Internal arc proofed 21kA/1sec A-FLR
  • Earthing of both the entire switchboard structure and the metal division between compartments
  • Mechanical interlocks assure exact operation sequence
  • Protection classes: PI (insulating partition)
  • Loss of service continuity classes: LSC2A (LSC1 for bus riser)
  • IP3X protection degree on the external housing
Optimization
  • Reduced dimension and weight
  • Less space requirement for switchboard installation
  • Easy integration in factory-built outdoor substations
  • Adapted solutions to cable connection
  • Modular units containing fixed and withdrawable metal-enclosed switchgear, using vacuum
Simplicity
  • Simplified switchboard busbar design
  • Mimic diagram in front of the switchboard using simple and functional devices

Specification

Rating Specification
Rated voltage kV 12 17.5 24
Rated frequency Hz 50/60
Power frequency withstand voltage
(Insulation/Isolation)
kV, rms (1min) 28 / 32 38 / 45 50 / 60
Lightning impulse withstand voltage
(Insulation/Isolation)
kV, peak
( 1.2 X 50 ㎲)
75 / 85 95 / 110 125 / 145
Rated frequency A 630
Short-time withstand current kA/s 16kA/3s, 21kA/3s, 25kA/1s
Making capacity (50Hz) kA 40 / 50 / 54.6
Internal arc classification kA/1s 21 (A-FLR): Option
Rating Specification
Rated voltage kV 12 17.5 24
Rated frequency Hz 50/60
Power frequency withstand voltage
(Insulation/Isolation)
kV, rms (1min) 28 / 32 38 / 45 50 / 60
Lightning impulse withstand voltage
(Insulation/Isolation)
kV, peak
( 1.2 X 50 ㎲)
75 / 85 95 / 110 125 / 145
Rated frequency A 630
Short-time withstand current kA/s 16kA/3s, 21kA/3s, 25kA/1s
Making capacity (50Hz) kA 40 / 50 / 54.6
Internal arc classification kA/1s 21 (A-FLR): Option