Features

Measurement Function
  • High precision measurement of various measurement elements (35 elements)
  • Extended power quality measurement (63th, THD, TDD, K-factor, Crest factor)
  • Event recording (20~1024 samples)
  • Select Before Operating (SBO) Function
  • Automatic Power Factor Control (APFC) (optional)
  • Transient wave and event measurement
Convenience Function
  • Color touch graphic LCD
  • Language and user selection menu
  • Manager software for PC connection
  • Statistics and trends for measurement elements
  • Add-ons
Communication Function
  • Various communication functions (3 ports)
Measurement Function
  • High precision measurement of various measurement elements (35 elements)
  • Extended power quality measurement (63th, THD, TDD, K-factor, Crest factor)
  • Event recording (20~1024 samples)
  • Select Before Operating (SBO) Function
  • Automatic Power Factor Control (APFC) (optional)
  • Transient wave and event measurement
Convenience Function
  • Color touch graphic LCD
  • Language and user selection menu
  • Manager software for PC connection
  • Statistics and trends for measurement elements
  • Add-ons
Communication Function
  • Various communication functions (3 ports)

Measurement

Type Measuring item Datiled measuring item Accuracy
Voltage (V) Line voltage Vab, Vbc, Vca, Vlavg Note 0.2%
Phase voltage Va, Vb, Vc, Vnavg 0.2%
Normal, reversed-phase voltage V1, V2 -
Crest Factor Vab, Vbc, Vca, Va, Vb, Vc -
Current Phase current Ia, Ib, Ic, Iavg 0.2%
XPhase current Ix 0.2%
Normal, reversed-phase currents I1, I2 -
Crest Factor Ia, Ib, Ic -
Phase Line voltage ∠Vab, ∠Vbc, ∠Vca 0.5°
Phase voltage ∠Va, ∠Vb, ∠Vc 0.5°
Phase current ∠Ia, ∠Ib, ∠Ic, ∠Ix 0.5°
Electricity Active power Pa, Pb, Pc, ΣP 0.5class
Reactive power Qa, Qb, Qc, ΣQ 0.5class
Apparent power Sa, Sb, Sc, ΣS 0.5class
Electricity energy Active energy WHa, WHb, WHc, ΣWH 0.5class
Reactive energy VARHa, VARHb, VARHc, ΣVARH 0.5class
Reverse active energy rWHa, rWHb, rWHc, ΣrWH 0.5class
Reverse reactive energy rVARHa, rVARHb, rVARHc, ΣrVARH 0.5class
Apparent energy VAHa, VAHb, VAHc, ΣVAH 0.5class
freq Frequency F(Hz) 0.1%
Power Factor Power Factor(PF) Power Factor Power Factor(PF) PFa, PFb, PFc, ΣPF phase phase accuracy
1st harmonic power factor (DPF) DPFa, DPFb, DPFc, ΣDPF
Harmonics Line voltage Vab, Vbc, Vca 2~63th Harmonics -
Phase voltage Va, Vb, Vc 2~63th Harmonics
Phase current Ia, Ib, Ic 2~63th Harmonics -
THD Vab, Vbc, Vca, Va, Vb, Vc, Ia, Ib, Ic
TDD Ia, Ib, Ic
K-FACTOR Ia, Ib, Ic
AI 4~20mA AI01, AI02 0.5%

Note : Average of line voltage

Type Measuring item Datiled measuring item Accuracy
Voltage (V) Line voltage Vab, Vbc, Vca, Vlavg Note 0.2%
Phase voltage Va, Vb, Vc, Vnavg 0.2%
Normal, reversed-phase voltage V1, V2 -
Crest Factor Vab, Vbc, Vca, Va, Vb, Vc -
Current Phase current Ia, Ib, Ic, Iavg 0.2%
XPhase current Ix 0.2%
Normal, reversed-phase currents I1, I2 -
Crest Factor Ia, Ib, Ic -
Phase Line voltage ∠Vab, ∠Vbc, ∠Vca 0.5°
Phase voltage ∠Va, ∠Vb, ∠Vc 0.5°
Phase current ∠Ia, ∠Ib, ∠Ic, ∠Ix 0.5°
Electricity Active power Pa, Pb, Pc, ΣP 0.5class
Reactive power Qa, Qb, Qc, ΣQ 0.5class
Apparent power Sa, Sb, Sc, ΣS 0.5class
Electricity energy Active energy WHa, WHb, WHc, ΣWH 0.5class
Reactive energy VARHa, VARHb, VARHc, ΣVARH 0.5class
Reverse active energy rWHa, rWHb, rWHc, ΣrWH 0.5class
Reverse reactive energy rVARHa, rVARHb, rVARHc, ΣrVARH 0.5class
Apparent energy VAHa, VAHb, VAHc, ΣVAH 0.5class
freq Frequency F(Hz) 0.1%
Power Factor Power Factor(PF) Power Factor Power Factor(PF) PFa, PFb, PFc, ΣPF phase phase accuracy
1st harmonic power factor (DPF) DPFa, DPFb, DPFc, ΣDPF
Harmonics Line voltage Vab, Vbc, Vca 2~63th Harmonics -
Phase voltage Va, Vb, Vc 2~63th Harmonics
Phase current Ia, Ib, Ic 2~63th Harmonics -
THD Vab, Vbc, Vca, Va, Vb, Vc, Ia, Ib, Ic
TDD Ia, Ib, Ic
K-FACTOR Ia, Ib, Ic
AI 4~20mA AI01, AI02 0.5%

Note : Average of line voltage

APEC

Type APEC
BANK setting BANK number 0-8
Alarm number 0-1
Capacitor capacitance setting None ~ 999MVA
Alarm contact setting Setting one of extra contact out of DO_01~DO_08
Capacitor closing delay time 10~300sec / 1sec
Dead time (time for charge or discharge) 10~300sec / 1sec
Maximum power factor setting 0.95~1~ -0.90 ( - : indicating lead phase)
Minimum power factor setting 0.80 ~ 0.95
Alarm power factor setting (Alarm occurred) 0.00 ~ 0.90
Event occurrence
Under Voltage
and control Over PF
Low Current Set whether to get EVENT occurred or set the control in case the average current of 3 phase is 1A
Under Voltage Set whether to get EVENT occurred or set the control in case phase voltage ( 3 phase 3 wire, open delta, line voltage)
Over PF Set whether to get EVENT occurred or not when over Max. PF
Under PF Set whether to get EVENT occurred or not when over Min. PF
Over Volt THD Set whether to get EVENT occurred and BANK control or not when THD is above the setpoint
Power Factor control Automatic control Auto
Manual control Manual
Combination control In case all capacitances are set
Circulation control Capacitor In case capacitances are not set - Opening the closed one first and closing the opened last
Type APEC
BANK setting BANK number 0-8
Alarm number 0-1
Capacitor capacitance setting None ~ 999MVA
Alarm contact setting Setting one of extra contact out of DO_01~DO_08
Capacitor closing delay time 10~300sec / 1sec
Dead time (time for charge or discharge) 10~300sec / 1sec
Maximum power factor setting 0.95~1~ -0.90 ( - : indicating lead phase)
Minimum power factor setting 0.80 ~ 0.95
Alarm power factor setting (Alarm occurred) 0.00 ~ 0.90
Event occurrence
Under Voltage
and control Over PF
Low Current Set whether to get EVENT occurred or set the control in case the average current of 3 phase is 1A
Under Voltage Set whether to get EVENT occurred or set the control in case phase voltage ( 3 phase 3 wire, open delta, line voltage)
Over PF Set whether to get EVENT occurred or not when over Max. PF
Under PF Set whether to get EVENT occurred or not when over Min. PF
Over Volt THD Set whether to get EVENT occurred and BANK control or not when THD is above the setpoint
Power Factor control Automatic control Auto
Manual control Manual
Combination control In case all capacitances are set
Circulation control Capacitor In case capacitances are not set - Opening the closed one first and closing the opened last

Specification

Rating Specification
Wiring system 3P4W, 3P3W(Y), 3P3W(OPEN-DELTA), 1P3W, 1P2W
Rated frequency 60Hz or 50Hz
Measuring voltage range 10 ~ 452V(Va, Vb, Vc - Vn voltage at both terminals)
Measuring current range 0.05 ~ 6A
PT, CT input burden each less than 0.2VA
Rated Controlled power DC 110V±20%
Digital Input Power DI 6 Point (DC 110V)
Power Consumption 20W or less normally, 30W or less at operation
DO rated output DO 1~7 RELAY AC 250V 5A, DC 30V 5A Resistive load (COSθθ= 1)
DO 8 RELAY (C contacts) AC 250V 16A, DC 30V 16A
CB_ON, CB_OFF RELAY AC 250V 16A, DC 30V 16A
Operating temperature -10℃ ~ 55℃
Storage temperature -25℃ ~ 75℃
Operating humidity Within 80% RH, no condensation
Altitude Less than 2,000 m above sea level
Insulation Resistance Over DC 10㏁ / 5㏁
Insulation Voltage AC 2kV (1kV) / 1min
Impulse Voltage AC 5kV (3kV) / 1.2×50㎲
Overload withstand Current 2 In for 3 hours, 20 In for 2 seconds
Voltage 1.15 Vn for 3 hours
Fast Transient Disturbance Power Input 4kV, Other Input 2kV (Analog Input 1kV)
ESD(Electrostatic Discharge) Air 8kV, Contact 6kV
Standards IEC 60255, IEC 61326, IEC 61000-4, KEMC 1110
Communication type MODBUS-TCP • MODBUS TCP(10/100 Base-Tx) : 1Port
• Communication speed : 10/100 MBps, Star Type, UTP (CAT.3, CAT.5)
• Communication distance, max.100m (HUB to terminal)
MODBUS-RTU • MODBUS RTU(RS485) : 2Ports
• Operation mode Differential, Universal 9,600 / 19,200/38,400bps
• Communication distance, max 1.2km, Universal RS485 Shielded twisted pair cable
• Transmission system, max Half-Duplex, output voltage -7V ~ +12V
Size / Weight (W×H×D) 190×255×116(mm), 3.6kg

※ Avoid places with vibration, shock, dust, moisture, corrosive, gas, etc.

Rating Specification
Wiring system 3P4W, 3P3W(Y), 3P3W(OPEN-DELTA), 1P3W, 1P2W
Rated frequency 60Hz or 50Hz
Measuring voltage range 10 ~ 452V(Va, Vb, Vc - Vn voltage at both terminals)
Measuring current range 0.05 ~ 6A
PT, CT input burden each less than 0.2VA
Rated Controlled power DC 110V±20%
Digital Input Power DI 6 Point (DC 110V)
Power Consumption 20W or less normally, 30W or less at operation
DO rated output DO 1~7 RELAY AC 250V 5A, DC 30V 5A Resistive load (COSθθ= 1)
DO 8 RELAY (C contacts) AC 250V 16A, DC 30V 16A
CB_ON, CB_OFF RELAY AC 250V 16A, DC 30V 16A
Operating temperature -10℃ ~ 55℃
Storage temperature -25℃ ~ 75℃
Operating humidity Within 80% RH, no condensation
Altitude Less than 2,000 m above sea level
Insulation Resistance Over DC 10㏁ / 5㏁
Insulation Voltage AC 2kV (1kV) / 1min
Impulse Voltage AC 5kV (3kV) / 1.2×50㎲
Overload withstand Current 2 In for 3 hours, 20 In for 2 seconds
Voltage 1.15 Vn for 3 hours
Fast Transient Disturbance Power Input 4kV, Other Input 2kV (Analog Input 1kV)
ESD(Electrostatic Discharge) Air 8kV, Contact 6kV
Standards IEC 60255, IEC 61326, IEC 61000-4, KEMC 1110
Communication type MODBUS-TCP • MODBUS TCP(10/100 Base-Tx) : 1Port
• Communication speed : 10/100 MBps, Star Type, UTP (CAT.3, CAT.5)
• Communication distance, max.100m (HUB to terminal)
MODBUS-RTU • MODBUS RTU(RS485) : 2Ports
• Operation mode Differential, Universal 9,600 / 19,200/38,400bps
• Communication distance, max 1.2km, Universal RS485 Shielded twisted pair cable
• Transmission system, max Half-Duplex, output voltage -7V ~ +12V
Size / Weight (W×H×D) 190×255×116(mm), 3.6kg

※ Avoid places with vibration, shock, dust, moisture, corrosive, gas, etc.