Benefits
Uncompromised Operator Safety
- Arc-free zone structure to prevent interrupting accidents between phases
- Logical mechanical and electrical interlock to prevent improper operations
- Modularization of components for simple treatment
- Displays an electric current and operating conditions
Top-Tier Level of Reliability
- Obtained a new excellent technology (NET) certification for the eco-friendly epoxy resin embedded vacuum interrupter
- M2, E2, and C2 endurance class of vacuum interrupters
- Performed by high-quality vacuum interrupters with permanent magnetic actuators
- Verified a wide range of tests in association with insulation performance
Minimum Operating Costs
- Compact design of panels for minimum space requirement
- Combination of modular and flexible designs to effectively reduce the operating cost
- Easily accessible to the elbow cable and busbar
Uncompromised Operator Safety
- Arc-free zone structure to prevent interrupting accidents between phases
- Logical mechanical and electrical interlock to prevent improper operations
- Modularization of components for simple treatment
- Displays an electric current and operating conditions
Top-Tier Level of Reliability
- Obtained a new excellent technology (NET) certification for the eco-friendly epoxy resin embedded vacuum interrupter
- M2, E2, and C2 endurance class of vacuum interrupters
- Performed by high-quality vacuum interrupters with permanent magnetic actuators
- Verified a wide range of tests in association with insulation performance
Minimum Operating Costs
- Compact design of panels for minimum space requirement
- Combination of modular and flexible designs to effectively reduce the operating cost
- Easily accessible to the elbow cable and busbar
Specification
Rating |
Specification |
Model |
LCS-25F-25B |
LCS-25M-25B |
LSAE-K2-103 |
Rated Voltage (kV, rms) |
25.8 |
25.8 |
24 / 25.8 |
Rated Breaking Current (kA, rms) |
25 |
25 |
25 |
Rated Nominal Current (A, rms) |
630 |
2000 |
630 / 1250 |
Rated Frequency (Hz) |
60 |
60 |
60 |
Rated Duration of Short-circuit (S) |
1 |
1 |
3 |
Rated Peak Withstand Current (kA, Peak) |
65 |
65 |
65 |
Rated Power Frequency Withstand Voltage (kV, rms) |
70 |
70 |
60 / 70 |
Rated Lightning Impulse Withstand Voltage (kV, 1.2 X 50 ㎲) |
150 |
150 |
125 / 150 |
Degree of Protection (IP) |
4X |
4X |
4X |
Insulation Material |
Epoxy Resin |
Epoxy Resin |
Epoxy Resin |
Applicable Standards |
IEC 62271-1, 100, 102, 200 / GS 5925-0128 |
IEC 62271-1, 100, 102, 200 / GS 5925-0128 |
IEC 62271-1, 100, 102, 200 |
Rating |
Specification |
Model |
LCS-25F-25B |
LCS-25M-25B |
LSAE-K2-103 |
Rated Voltage (kV, rms) |
25.8 |
25.8 |
24 / 25.8 |
Rated Breaking Current (kA, rms) |
25 |
25 |
25 |
Rated Nominal Current (A, rms) |
630 |
2000 |
630 / 1250 |
Rated Frequency (Hz) |
60 |
60 |
60 |
Rated Duration of Short-circuit (S) |
1 |
1 |
3 |
Rated Peak Withstand Current (kA, Peak) |
65 |
65 |
65 |
Rated Power Frequency Withstand Voltage (kV, rms) |
70 |
70 |
60 / 70 |
Rated Lightning Impulse Withstand Voltage (kV, 1.2 X 50 ㎲) |
150 |
150 |
125 / 150 |
Degree of Protection (IP) |
4X |
4X |
4X |
Insulation Material |
Epoxy Resin |
Epoxy Resin |
Epoxy Resin |
Applicable Standards |
IEC 62271-1, 100, 102, 200 / GS 5925-0128 |
IEC 62271-1, 100, 102, 200 / GS 5925-0128 |
IEC 62271-1, 100, 102, 200 |