GIPAM1000
Home
Smart Power Solution
Protection/Measurement/Meter
Protection
Features
Protection function
- With 24 types of protection elements in 2 models, the distribution system protected
- Enhanced analysis function through various saved event data (up to 1,000 events are saved)
- Simple Trip logic Function
- Select Before Operating (SBO) and Check Before Operating (CBO)
- Vector diagram
- Sequence of Event (SOE)
- PT (VT) failure detection
- Circuit Breaker Failure (CBF)
- Disk emulation
Convenience function
- Self-diagnosis and sequence monitoring
- HMI with enhanced visibility and convenience
- Long-life and reliable parts applied
Communication function
- Universal communication (MODBUS/RS-485)
Protection function
- With 24 types of protection elements in 2 models, the distribution system protected
- Enhanced analysis function through various saved event data (up to 1,000 events are saved)
- Simple Trip logic Function
- Select Before Operating (SBO) and Check Before Operating (CBO)
- Vector diagram
- Sequence of Event (SOE)
- PT (VT) failure detection
- Circuit Breaker Failure (CBF)
- Disk emulation
Convenience function
- Self-diagnosis and sequence monitoring
- HMI with enhanced visibility and convenience
- Long-life and reliable parts applied
Communication function
- Universal communication (MODBUS/RS-485)
Protection
Type |
Usage |
Protection Elements |
GIPAM1000 FI |
Feeder (13 Type) |
OCR (50/51)
UVR (27)
LOCK-OUT (86) |
OCGR (50N/51N)
OVR (59)
CBF (50BF) |
SGR (67G)
OVGR (64)
PTF (60F) |
SEF (51S)
POR (47P) |
GIPAM1000 DG |
Distributed Generator (25 Type) |
OCR (50/51)
UVR (27)
LOCK-OUT (86)
DOCGR (67NI/ND)
UFR (81U)
UCR (37) |
OCGR (50N/51N)
OVR (59)
CBF (50BF)
DPR (32P)
OFR (81O)
WS (78V) |
SGR (67G)
OVGR (64)
PTF (60F)
DQR (32Q)
ROCOF (81R) |
SEF (51S)
POR (47P)
SYNC (25)
DOCR (67I/67D)
UPR (37P) |
Type |
Usage |
Protection Elements |
GIPAM1000 FI |
Feeder (13 Type) |
OCR (50/51)
UVR (27)
LOCK-OUT (86) |
OCGR (50N/51N)
OVR (59)
CBF (50BF) |
SGR (67G)
OVGR (64)
PTF (60F) |
SEF (51S)
POR (47P) |
GIPAM1000 DG |
Distributed Generator (25 Type) |
OCR (50/51)
UVR (27)
LOCK-OUT (86)
DOCGR (67NI/ND)
UFR (81U)
UCR (37) |
OCGR (50N/51N)
OVR (59)
CBF (50BF)
DPR (32P)
OFR (81O)
WS (78V) |
SGR (67G)
OVGR (64)
PTF (60F)
DQR (32Q)
ROCOF (81R) |
SEF (51S)
POR (47P)
SYNC (25)
DOCR (67I/67D)
UPR (37P) |
Specification
Type |
Specification |
Wiring |
3P3W (2PT-D), 3P4W (3PT-Y) |
Rating |
Frequancy |
60Hz, 50Hz Note) |
Voltage |
PT |
110V (55~125V) |
GPT |
Vn*√3 Vn: PT secondary rating voltage |
Current |
CT |
5A |
ZCT |
1.5mA |
Power |
AC/DC110V, DC125V |
Power consumption |
30W or less: Stanby / 50W or less: Operation |
Burden |
0.5VA or less: PT
1.0VA or less: CT |
Input contact |
for general |
Digital Input AC/DC 110V, DC125V |
Output contact |
for trip |
AC 250V 15A/DC 30V 15A, Resistive Load: Rated Capacity
AC 4000VA, DC 480W: Opening Capacity |
for alarm |
AC 250V 10A/DC 30V 10A, Resistive Load: Closed Capacity
AC 1250VA, DC 150W: Opening Capacity |
Tolerance |
Operation Value |
±5% |
Operation Time |
±5% or ±35ms |
OInsulation Resistance |
DC 500V 100MΩ or more |
Insulation Voltage |
AC 2kV (1kV)/1min |
Lightning impulse voltage |
AC 5kV (3kV) or more, 1.2x50μs standard waveform supplied |
Overload withstand |
Current circuit |
Withstand 1.2 times of rated current continuously
Withstand 2 times of rated current for 3 hours.
Withstand 20 times of rated current for 2 seconds.
Withstand 40 times of rated current for 1 second. |
Voltage circuit |
Withstand 1.15 times of rated voltage for 3 hours. |
Fast Transient Disturbance |
4kV: power input
2kV: other input |
Electrostatic Discharge (ESD) |
8kV: Air, 6kV: Contact |
Temperature |
Operation |
-25℃ ~ 60℃ |
Storage |
-40℃ ~ 70℃ |
Humidity |
RH 80% or less (non-condensing) |
Altitude |
2,000m or less |
Environment |
A place not subject to abnormal vibration and shock. |
Applied Standards |
KEMC 1120 |
Dimension (mm) |
196 (W) x 254 (H) x 220 (D): Cutting Size |
Weignt |
6.78kg |
Communication |
RS-485: Modbus |
Note) Contact us.
Type |
Specification |
Wiring |
3P3W (2PT-D), 3P4W (3PT-Y) |
Rating |
Frequancy |
60Hz, 50Hz Note) |
Voltage |
PT |
110V (55~125V) |
GPT |
Vn*√3 Vn: PT secondary rating voltage |
Current |
CT |
5A |
ZCT |
1.5mA |
Power |
AC/DC110V, DC125V |
Power consumption |
30W or less: Stanby / 50W or less: Operation |
Burden |
0.5VA or less: PT
1.0VA or less: CT |
Input contact |
for general |
Digital Input AC/DC 110V, DC125V |
Output contact |
for trip |
AC 250V 15A/DC 30V 15A, Resistive Load: Rated Capacity
AC 4000VA, DC 480W: Opening Capacity |
for alarm |
AC 250V 10A/DC 30V 10A, Resistive Load: Closed Capacity
AC 1250VA, DC 150W: Opening Capacity |
Tolerance |
Operation Value |
±5% |
Operation Time |
±5% or ±35ms |
OInsulation Resistance |
DC 500V 100MΩ or more |
Insulation Voltage |
AC 2kV (1kV)/1min |
Lightning impulse voltage |
AC 5kV (3kV) or more, 1.2x50μs standard waveform supplied |
Overload withstand |
Current circuit |
Withstand 1.2 times of rated current continuously
Withstand 2 times of rated current for 3 hours.
Withstand 20 times of rated current for 2 seconds.
Withstand 40 times of rated current for 1 second. |
Voltage circuit |
Withstand 1.15 times of rated voltage for 3 hours. |
Fast Transient Disturbance |
4kV: power input
2kV: other input |
Electrostatic Discharge (ESD) |
8kV: Air, 6kV: Contact |
Temperature |
Operation |
-25℃ ~ 60℃ |
Storage |
-40℃ ~ 70℃ |
Humidity |
RH 80% or less (non-condensing) |
Altitude |
2,000m or less |
Environment |
A place not subject to abnormal vibration and shock. |
Applied Standards |
KEMC 1120 |
Dimension (mm) |
196 (W) x 254 (H) x 220 (D): Cutting Size |
Weignt |
6.78kg |
Communication |
RS-485: Modbus |
Note) Contact us.