Features

Measurement Function
  • High precision measurement of various measurement elements (11 elements)
  • Wide range of PT voltage inputs
  • DC voltage and DC current measurement
Convenience Function
  • Compact appearance and panel cutting size
  • Support for wide voltage environment (AC/DC 88~264V)
Communication Function
  • Communication redundancy
Measurement Function
  • High precision measurement of various measurement elements (11 elements)
  • Wide range of PT voltage inputs
  • DC voltage and DC current measurement
Convenience Function
  • Compact appearance and panel cutting size
  • Support for wide voltage environment (AC/DC 88~264V)
Communication Function
  • Communication redundancy

Measurement

Type Measurement Accuracy(%)
AC voltage AC voltage Vac ±0.30%
frequency Hz ±0.05Hz
THD THD -
DC voltage DC voltage Vdc ±0.30%
DC current Output current Iout ±0.50%
Battery current Battery current Battery current
MAX AC voltage MAX Vac -
THD MAX THD -
DC voltage MAX Vdc -
Output current MAX Iout -
Battery current MAX Ibat -
Type Measurement Accuracy(%)
AC voltage AC voltage Vac ±0.30%
frequency Hz ±0.05Hz
THD THD -
DC voltage DC voltage Vdc ±0.30%
DC current Output current Iout ±0.50%
Battery current Battery current Battery current
MAX AC voltage MAX Vac -
THD MAX THD -
DC voltage MAX Vdc -
Output current MAX Iout -
Battery current MAX Ibat -

Specification

Rating Specification
Input Frequency 50Hz / 60Hz
Voltage PT AC 20~452V, DC 20~264V
Control voltage AC/DC 88~264V (Free voltage)
Power consumption Max. 10W
Burden PT Max. 0.5VA
Insulation Resistance Over DC 500V 100㏁
Insulation Voltage AC 2kV (1kV) / 1min
Impulse Voltage AC 5kV (3kV) / 1.2×50㎲
Overload withstand Current circuit 1.2 In for 3 hours
8 In for 2 seconds
Voltage circuit 1.15 Vn for 3 hours
Fast Transient/Burst Immunity Power Input 4kV
DC Input 2kV
ESD(Electrostatic Discharge) Air 8kV
Contact 6kV
Operation temperature -10℃ ~ 55℃
Storage temperature -25℃ ~ 70℃
Humidity Within 80% RH, no condensation
Altitude 2000m and below
Others Non-impact place
Non-air pollution place
Standard IEC60255, IEC61000-4
Communication MODBUS/RS485
Dimension(W×H×D) 144×144×85 (mm)
Rating Specification
Input Frequency 50Hz / 60Hz
Voltage PT AC 20~452V, DC 20~264V
Control voltage AC/DC 88~264V (Free voltage)
Power consumption Max. 10W
Burden PT Max. 0.5VA
Insulation Resistance Over DC 500V 100㏁
Insulation Voltage AC 2kV (1kV) / 1min
Impulse Voltage AC 5kV (3kV) / 1.2×50㎲
Overload withstand Current circuit 1.2 In for 3 hours
8 In for 2 seconds
Voltage circuit 1.15 Vn for 3 hours
Fast Transient/Burst Immunity Power Input 4kV
DC Input 2kV
ESD(Electrostatic Discharge) Air 8kV
Contact 6kV
Operation temperature -10℃ ~ 55℃
Storage temperature -25℃ ~ 70℃
Humidity Within 80% RH, no condensation
Altitude 2000m and below
Others Non-impact place
Non-air pollution place
Standard IEC60255, IEC61000-4
Communication MODBUS/RS485
Dimension(W×H×D) 144×144×85 (mm)